Wire Gauge vs Amp Chart for Residential Wiring (AWG to Breaker Size)
Residential Copper Wire Gauge vs Ampacity Chart (NEC Table 310.16)
This table applies to insulated copper conductors at 30°C (86°F) ambient temperature with no more than three current-carrying conductors bundled together in a cable or raceway.
| Wire Size (AWG) | 60°C Rating (NM-B / UF-B) | 75°C Rating (THWN / XHHW in Conduit) | 90°C Insulation Rating | NEC 240.4(D) Max Breaker | Common Residential Use |
|---|---|---|---|---|---|
| 14 AWG | 15 A | 20 A* | 25 A* | 15 A | Lighting, bedroom/living room 15A circuits |
| 12 AWG | 20 A | 25 A* | 30 A* | 20 A | Kitchen, bath, laundry, garage 20A outlets |
| 10 AWG | 30 A | 35 A* | 40 A* | 30 A | Electric dryers, 30A water heaters |
| 8 AWG | 40 A | 50 A | 55 A | — | 40A ranges, EV chargers (50A only with 75°C wiring) |
| 6 AWG | 55 A | 65 A | 75 A | — | 50A ranges/EV outlets (NM-B); 60A subpanel (THHN) |
| 4 AWG | 70 A | 85 A | 95 A | — | 70A subpanel feeders |
| 3 AWG | 85 A | 100 A | 115 A | — | 100A subpanel feeders (THHN/SER) |
| 2 AWG | 95 A | 115 A | 130 A | — | 100A subpanels (NM-B), 100A+ feeders |
| 1/0 AWG | 125 A | 150 A | 170 A | — | 150A service/feeders |
*Even though 14, 12, and 10 AWG show higher numbers in the 75°C and 90°C columns, NEC 240.4(D) caps their overcurrent protection at 15 A, 20 A, and 30 A for normal branch circuits. Those higher columns are only used as starting points for temperature or bundling derating math.
Why Wire Has Three Temperature Columns
Every homeowner gets tripped up by reading the jacket on modern wire. Look closely at a spool of THHN or even the individual copper wires stripped out of yellow 12/2 NM-B Romex and you'll see 90°C insulation printed right on them. That does not mean you get to put 12 AWG on a 30-amp breaker.
Two separate NEC rules pull that number back down:
- The Termination Rule (NEC 110.14(C)): Your circuit is only as heat-tolerant as its weakest connection. For equipment rated 100 amps or less (or 14 AWG through 1 AWG wire), you must use the 60°C column unless every breaker, receptacle, and lug on the circuit is listed and marked for 75°C. Most modern breakers carry 60°C/75°C markings, yet standard wall outlets and switches often don't support 75°C branch ratings, and NM-B adds a stricter cap anyway.
- The NM-B Rule (NEC 334.80): Nonmetallic-sheathed cable (Romex) must never exceed the 60°C ampacity column regardless of what its internal wires are rated for. That is why 6/3 NM-B Romex tops out at 55 amps and cannot feed a 60-amp EV charger hardwired at full 60 A breaker rating. Switch to 6 AWG copper THHN inside EMT or PVC conduit on 75°C terminals and it sits in the 75°C column at 65 amps, which works cleanly on a 60-amp breaker.
Aluminum and Copper-Clad Aluminum Sizes
Aluminum wire isn't used for ordinary 15- and 20-amp branch circuits in modern homes. Still, it is very common for 100-amp to 200-amp service entrances, main subpanel feeders, and large 50A–90A runs using SER or XHHW-2 cable because it costs a fraction of copper.
| Aluminum Size (AWG) | 60°C Rating | 75°C Rating | Common Residential Use |
|---|---|---|---|
| 8 AWG Al | 35 A | 40 A | 40A branch or small feeder (75°C) |
| 6 AWG Al | 40 A | 50 A | 50A feeder / subpanel (75°C) |
| 4 AWG Al | 55 A | 65 A | 60A subpanel feeder (75°C) |
| 2 AWG Al | 75 A | 90 A | 90A subpanel (or 100A dwelling main service per NEC 310.12) |
| 1/0 AWG Al | 100 A | 120 A | 120A feeder (100A–125A main service rules differ) |
| 4/0 AWG Al | 150 A | 180 A | 200A residential main service (per NEC 310.12) |
Notice one special exception people read about online: NEC 310.12 allows a slightly smaller conductor (such as 2 AWG aluminum or 4 AWG copper for 100 A, and 4/0 AWG aluminum or 2/0 AWG copper for 200 A) strictly for the main service or feeder supplying the entire dwelling unit load. That exception does not apply to a garage or workshop subpanel, where Table 310.16 still governs.
When You Have to Size Up for Voltage Drop or Heat
Ampacity tells you how much current a wire can carry without melting its insulation. It does not tell you how much voltage gets lost along a long yard run to a detached shed or well pump.
NEC informational notes suggest keeping voltage drop under 3% on a branch circuit (and 5% combined across feeder plus branch) for reasonable efficiency. On a 120-volt, 15-amp run reaching 150 feet to an outbuilding, 14 AWG will safely handle the amps without overheating, yet tools and motors at the far end may struggle from low voltage. Stepping up one gauge to 12 AWG, or 10 AWG for long 20-amp runs, solves voltage drop without changing the breaker size. Remember, putting thicker wire on a smaller breaker is always allowed as long as the wire physically fits the breaker and device terminals.
Frequently Asked Questions
Can I put 14 AWG wire on a 20-amp breaker?
No. NEC 240.4(D) limits 14 AWG copper overcurrent protection to 15 amps maximum. Putting a 20-amp breaker on 14 AWG wire allows the wire to overheat before the breaker trips.
Can I use 12 AWG wire on a 15-amp breaker?
Yes. Oversizing wire for a smaller breaker is always code-compliant and is often done to reduce voltage drop on long runs. Just confirm the terminals on the breaker and switch accept 12 AWG.
Why is 6 AWG Romex rated at 55 amps instead of 65 amps?
NEC 334.80 restricts NM-B (Romex) cable to the 60°C column of Table 310.16, where 6 AWG copper equals 55 A. Individual 6 AWG THHN wires in conduit on 75°C terminals can use the 75°C column (65 A).
What size wire is needed for a 100-amp subpanel?
At 75°C termination ratings, a 100-amp subpanel feeder requires 3 AWG copper (100 A) or 1 AWG aluminum (100 A) under Table 310.16. The 2 AWG aluminum / 4 AWG copper allowance in NEC 310.12 applies only to the main service or feeder carrying the entire dwelling load.
- NFPA 70 (National Electrical Code) 2023 — Table 310.16, Section 110.14(C), Section 240.4(D), Section 310.12, and Section 334.80
- Southwire / CME Wire NM-B & UF-B Technical Ampacity Data Sheets